Thefirststepincommissioning an
OnTrac®
systemwillbe the assignment of the addres s number
for each boiler. The following instructions are specific to the
TempTrac®.
If your boiler uses a
differentcontrolrefertotheprogramminginstructionforthatcontroltosetthecontroladdress.
1. EntertheProgrammingmodebypressingtheSetandDOWNkeyfor3s.
2. PresstheDOWNkey.
3. Select“Pr2”“PAS”parameterandpresstheSET key.
4. Thevalue“0‐‐withaflashingzeroisdisplayed.
5. Use UP or DOWN
keys to input the security code in the flashing
digits;confirmthefigurebypressingSET”.Thesecuritycodeis“321“.
6. Once you ha ve entered the Pr2 menu press the DOWN key three
timesandtheparameterAdrwillappe aronthescreenasfollows:
7. Nowpress
theSETkeyonceandthenumberwillbegintoblink.Use
thearrowkeytosettheaddressfrom(1to20).Theaddressrange(1
to12)isreservedforTier1boilersonly.Theaddressrange(13to20)
isreservedforTier2boilers.
8. Each
boilershouldbeassignedadifferentaddressinorderforpropercommunication tooccur.
The OnTrac®
may require that the real time
clockbesettomatchthelocaltime.
To change the time, go to the OPTION menu
and then the OPTION 2 TIME screen. Use the
individualdataentrybuttonsatthebottomleft
cornerof thescreen.TheSETDAY buttonis for
the
dayoftheweek1to7(SundaytoSaturday).
Remember to use a 24 hour clock for all
Ontrac®setupparameters.
ASSIGNING BOILER ADDRESSE
S
Adr
1
CHANGING THE TIME CLOC
K