The SYSTEM HISTORY screen will provide the user with a real time and historical log of four
preselected system temperatures as well as two additional temperatures the user can select. The
functionisalsopreprogrammedtorecorddataeveryfiveminutesandstoreupto10000scans.
The preselected
temperatures are as follows: System Temper ature, Outdoor Temperature,
Boiler1ReturnandBoiler2Return.
ThetwooptionalpenscanbeassignedtheReturnorSupplytemperatures ofanyboilerinthe
system. The schedule bel ow assigns a number to each of those temperatures if present in the
system.
Toassign anoptionalpenatemperature,touchthethumbwheelbutton andusethearrowsto
enterthenumberthenpresstheenterbutton.
o Numbers1to20aretheReturnTemperaturesforBoiler1to20.
o Numbers21to40aretheSupplyTemperaturesforBoilers1to
20.
Thearrowbuttonsatthetopofthescreenareusedtomovebackwardorforwardinthestream
ofdata.TheCLRbuttonwillclearallhistoricaldata.
SYSTEM HISTOR
Y